H05VV5-F

Oil resistant PVC sheathed flexible cables.

.
 
 

H05VV5-F Multi-core sheathed round flexible cable oil resistant

Rated voltage: Uo/U 300/500 V 

Standards: EN 50525-1, EN 50525-2-11 or EN 50525-2-51 for H05VV5-F, EN IEC 60332-1-2, EN IEC 60228.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: flexible annealed plain copper class 5 (EN IEC 60228).

Insulation: PVC of type TI2.

Colours of the cores:
Two-core: blue-brown;
Three-core: green/yellow-blue-brown or brown-black-grey;
Four-core: green/yellow-brown-black-grey or blue-brown-black-grey;
Five-core: green/yellow-blue-brown-black-grey or blue-brown-black-grey-black;
For the cables H05VV5-F black cores with white progressive numbering inscription are possible.

Sheath: PVC of type TM5.
Colour of the sheath: black or white or grey; if explicitly requested, and for agreed quantities, the cables can be supplied in other single colours.

Marking: continuous marking on the sheath: on one side « ICEL H05VV5-F IEMMEQU <HAR> »,
on the opposite side « nominal cross section, year of production, MADE IN ITALY ».

Minimum installation and handling temperature: + 5 °C 

Maximum operating temperature: 60 °C on the conductor.

Minimum usage temperature: - 10 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 150 °C on the conductor (for maximum 5 seconds).

Minimum internal bending radius:
For free movements: 5 times the overall diameter is less than  12 mm; 6 times if greater;
For fixed installations 3 times the greatest overall dimension if smaller than 12 mm; 4 times if greater;
For repeated wrappings 7 times the greatest overall dimension if smaller than 12 mm; 8 times if greater. 

Maximum tensile stress: 1,5 kg/mm² of the conductor cross section.

Current carrying capacity: see EN 50565-1 standard and CEI-UNEL 35024.
For cross-sections up to 1 mm²:
cross-section (mm²) 0,5 - 0,75 - 1
current (A)                   3   -    6    -    10

Guidance for Use: 
the cables are resistant to general purpose mineral oil.
Suitable for installations for manufacturing purposes including machines tools. Not suitable for continuous immersion in oil.

Further instructions and guidance for use are given in the EN 50565 standard.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.


 
.