Patriot FS17–450/750 V

Reaction to Fire CPR: Cca-s3,d1,a3

Single core non-sheathed power cable with PVC insulation, flexible conductors for fixed wiring, coloured with skin coating technology.
Resistant to fire propagation and with reduced emission of corrosive gases.

.
.
 
 
.
.
 
 
Nominal cross- sectional area of conductor
Maximum
diameter of
conductor wires
Thickness
of insulation
specified value
Maximum
overall
diameter
Indicative
cable
weight
Maximum
resistance
of conductor
at 20 °C
Minimum
insulation
resistance
at 70 °C
mm²
mm
mm
mm
g/m
ohm/km
Mohm•km
1
0,21
0,7
3,0
15
19,5
0,095
1,5
0,26
0,7
3,4
21
13,3
0,082
2,5
0,26
0,8
4,1
32
7,98
0,077
4
0,31
0,8
4,8
47
4,95
0,062
6
0,31
0,8
5,3
65
3,30
0,050
10
0,41
1,0
6,8
110
1,91
0,049

AFIAM PATRIOT FS17-450/750 V Single-core flexible cable

Rated voltage: Uo/U  450/750 V

Standards: EN 50525-1 p.q.a., EN 50525-2-31 p.q.a., CEI Unel 35752, EN 60228, CEI 20-22 II, EN 60332-1-2, EN 50267-2-1, EN 50575:2014+A1:2016.

Regulation Construction Products: 305/2011 EU.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: flexible annealed plain copper class 5 (EN IEC 60228).

Insulation: PVC of type S17 with low emission of corrosive gases if involved in a fire.

Insulation colour: blue, dark blue, black, brown, grey, green/yellow, red, white, turquoise, violet, orange, pink.

Marking: continuous marking on the insulation: on one side « ICEL AFIAM FS17-450/750 V  IEMMEQU EFP  Cca-s3,d1,a3 »,
on the opposite side « nominal cross section, year of production, MADE IN ITALY ».

Minimum installation and handling temperature: +5 °C

Maximum operating temperature: 70 °C on the conductor.

Minimum usage temperature: -10 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 160 °C on the conductor (for maximum 5 seconds).

Minimum permissible bending radii: 4 times the cable overall diameter.

Maximum tensile stress: 1,5 kg/mm² of the conductor cross section. 

Current carrying capacity: see EN 50565-1 standard and CEI-UNEL 35024. 

Guide to Use: For installations for which the standards require cables resistant to fire propagation; for installation in surface mounted or embedded conduits or pipes. Suitable for fixed protected installation in, or on, lighting or control gear for voltages up to 1000 V a.c. or, up to 750 V d.c. to earth.
The cross-section of 1 mm² is intended only for the electric circuits of lifts and elevators, or for the internal wiring of switchboards for signalling and control circuits.
FS17-450/750 V cables are suitable for general applications in construction work subject to fire reaction requirements; for bundle installations with high fire risks, having fire reaction class Cca-s3, d1, a3.

Further instructions and guidance for use are given in the EN 50565 standard.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.