FG17-450/750 V

Reaction to Fire CPR: Cca-s1b,d1,a1

Single core flexible power cable with G17 rubber insulation, resistant to fire propagation, having low emission of smoke and toxic and corrosive gases when exposed to fire.

.
.
.
.
.
 
 

Rated voltage: Uo/U  450/750 V

Standards: CEI 20-38, CEI Unel 35310, CEI 20-11, EN IEC 60228, EN IEC 60332-1-2, EN IEC 60754-2, EN 50267-2-1, EN IEC 61034-2, EN 50575:2014+A1:2016.

Regulation Construction Products: 305/2011 EU.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: flexible annealed plain copper class 5 EN IEC 60228.

Insulation: rubber compound of type G17, having low emission of smoke and toxic and corrosive gases when exposed to fire. 

Colour: blue, black, brown, grey, green/yellow, red, white, turquoise, violet, orange, pink.

Marking: continuous marking on the insulation: « LOMBARDA noSmoke ECOGAMMA FG17-450/750 V nominal cross section IEMMEQU EFP, year of production, MADE IN ITALY  Cca,s1b,d1,a1 ».

Minimum installation and handling temperature: - 15 °C

Maximum operating temperature: 90 °C on the conductor.

Minimum usage temperature: - 30 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 250 °C on the conductor (for maximum 5 seconds).

Minimum internal bending radii: 4 times the overall diameter if the cable diameter is lower than 8 mm; 5 times if between 8 and 12 mm; 6 times if over 12 mm.

Maximum tensile stress: 1,5 kg/mm² of the conductor cross section

Current carrying capacity: see EN 50565-1 standard and CEI-UNEL 35024.

Guidance for Use: for installation where high presence of people is foreseen and a low level of emission of smoke and corrosive gases are required in case of fire or burning. Installation in surface mounted or embedded conduits, or similar closed systems; suitable for fixed protected installation in, or on, lighting or control gear for voltages up to 1000 V a.c. or, up to 750 V d.c. to earth. 
Particular suitability for installation in bunches (according to the relative test conditions).
FG17-450/750 V cables are suitable for general applications in construction work subject to fire reaction requirements; for bundle installations with high fire risks, having fire reaction class Cca-s1b, d1, a1.

Further instructions and guidance for use are given in the EN 50565 and CEI 20-40 standards.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.

 
.