FG7OR–0,6/1 kV

Multicore power cables, G7 rubber insulated, PVC sheathed, with flexible conductors for fixed installations. Resistant to fire propagation with reduced emission of corrosive gases under fire conditions.

.
 
 
.
.
 
 

Tab. CEI-UNEL 35375

Number and nominal cross-sectional area of conductors
Maximum
diameter of
conductor wires
Thickness
of insulation
specified value
Indicative
core
diameter
Thickness
of sheath
specified value
Maximum
overall
diameter
Indicative
cable
weight
Maximum
resistance
of conductors
at 20 °C
mm²
mm
mm
mm
mm
mm
g/m
ohm/km
2 x 1,5
0,26
0,7
2,9
1,8
12,0
150
13,3
2 x 2,5
0,26
0,7
3,4
1,8
13,0
190
7,98
2 x 4
0,31
0,7
3,9
1,8
14,2
240
4,95
2 x 6
0,31
0,7
4,4
1,8
15,4
310
3,30
2 x 10
0,41
0,7
5,3
1,8
17,3
440
1,91
2 x 16
0,41
0,7
6,4
1,8
19,4
600
1,21
2 x 25
0,41
0,9
8,2
1,8
23,0
850
0,780
2 x 35
0,41
0,9
9,5
1,8
25,7
1130
0,554
2 x 50
0,41
1,0
11,2
1,8
29,3
1580
0,386
2 x 70
0,51
1,1
13,2
1,8
33,1
2050
0,272
2 x 95
0,51
1,1
14,7
2,0
37,4
2670
0,206
2 x 120
0,51
1,2
16,6
2,1
41,5
3330
0,161
2 x 150
0,51
1,4
18,6
2,2
46,1
4100
0,129
3 G 1,5
0,26
0,7
2,9
1,8
12,5
170
13,3
3 G 2,5
0,26
0,7
3,4
1,8
13,6
220
7,98
3 G 4
0,31
0,7
3,9
1,8
14,9
280
4,95
3 G 6
0,31
0,7
4,4
1,8
16,2
370
3,30
3 G 10
0,41
0,7
5,3
1,8
18,2
530
1,91
3 G 16
0,41
0,7
6,4
1,8
20,6
740
1,21
3 G 25
0,41
0,9
8,2
1,8
24,5
1060
0,780
3 G 35
0,41
0,9
9,5
1,8
27,3
1420
0,554
3 G 50
0,41
1,0
11,2
1,8
31,2
1960
0,386
3 G 70
0,51
1,1
13,2
1,9
35,6
2700
0,272
3 G 95
0,51
1,1
14,7
2,0
40,0
3430
0,206
3 G 120
0,51
1,2
16,6
2,1
44,4
4390
0,161
3 G 150
0,51
1,4
18,6
2,3
49,5
5400
0,129
3 G 185
0,51
1,6
20,7
2,4
55,2
6700
0,106
3 G 240
0,51
1,7
23,5
2,6
61,9
8700
0,0801
3 G 300
0,51
1,8
26,1
2,8
68,0
10700
0,0641
4 G 1,5
0,26
0,7
2,9
1,8
13,4
200
13,3
4 G 2,5
0,26
0,7
3,4
1,8
14,6
260
7,98
4 G 4
0,31
0,7
3,9
1,8
16,0
330
4,95
4 G 6
0,31
0,7
4,4
1,8
17,5
430
3,30
4 G 10
0,41
0,7
5,3
1,8
19,8
640
1,91
4 G 16
0,41
0,7
6,4
1,8
22,4
900
1,21
4 G 25
0,41
0,9
8,2
1,8
26,8
1300
0,780
3x35 +25
0,41
0,9
9,5 / 8,2
1,8
29,2
1650
0,554 / 0,780
3x50 +25
0,41
1,0 / 0,9
11,2 / 8,2
1,8
32,4
2200
0,386 / 0,780
3x70 +35
0,51 / 0,41
1,1 / 0,9
13,2 / 9,5
1,9
37,0
3000
0,272 / 0,554
3x95 +50
0,51 / 0,41
1,1 / 1,0
14,7 / 11,2
2,1
42,0
3900
0,206 / 0,386
3x120 +70
0,51
1,2 / 1,1
16,6 / 13,2
2,2
46,9
4700
0,161 / 0,272
3x150 +95
0,51
1,4 / 1,1
18,6 / 14,7
2,4
52,5
6300
0,129 / 0,206
3x185 +95
0,51
1,6 / 1,1
20,7 / 14,7
2,5
57,3
7600
0,106 / 0,206
3x240 +150
0,51
1,7 / 1,4
23,5 / 18,6
2,7
65,5
10000
0,0801 / 0,129
3x300 +150
0,51
1,8 / 1,4
26,1 / 18,6
2,9
70,8
12000
0,0641 / 0,129
5 G 1,5
0,26
0,7
2,9
1,8
14,4
230
13,3
5 G 2,5
0,26
0,7
3,4
1,8
15,6
310
7,98
5 G 4
0,31
0,7
3,9
1,8
17,3
400
4,95
5 G 6
0,31
0,7
4,4
1,8
18,9
520
3,30
5 G 10
0,41
0,7
5,3
1,8
21,5
780
1,91
5 G 16
0,41
0,7
6,4
1,8
24,4
1120
1,21
5 G 25
0,41
0,9
8,2
1,8
29,3
1680
0,780
5 G 35
0,41
0,9
9,5
1,8
32,8
2150
0,554
5 G 50
0,41
1,0
11,2
2,0
38,2
3000
0,386
 If explicitly requested, and for agreed quantities, a version of the cables without the protective conductor (green/yellow) can be supplied.
 
 

FG7OR–0,6/1 kV  Multicore flexible conductor

Nominal voltage: Uo/U  0,6/1 kV.

Maximum voltage: 1,8 kV d.c. also to earth

Standards: CEI 20-13, CEI 20-11; CEI EN e IEC 60228 (CEI 20-29); CEI 20-22 II, CEI EN 60332-1-2 (CEI 20- 35), CEI EN 50267-2-1 (CEI 20-37/2-1); HD 605-A1.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: flexible annealed plain copper class 5 CEI EN IEC 60228.

Insulation: hard ethylene propylene rubber (HEPR) compound, of type G7, with reduced emission of halogen (corrosive gases) under fire conditions.

Colour of the cores:
Two cores: blue – brown.
Three cores: blue – brown – green/yellow   or   brown – black – grey.
Four cores: brown – black – grey – green/yellow   or   blue – brown – black – grey.
Five cores: blue – brown – black – grey – green/yellow or blue – brown – black – grey – black.

Sheath: PVC of type Rz with reduced emission of halogen (corrosive gases) under fire conditions. Resistance to UV exposure, measured according to the CENELEC standard HD 605, for a sure outside non protected to sun light installation.
Colour:  light grey.

Marking: continuous marking on the sheath: « ICEL or LOMBARDA FG7OR-0,6/1 kV nominal cross section CEI 20-22 II IEMMEQU ECOGAMMA production date Made in Italy », with under the sheath the IEMMEQU thread.
Progressive meter marking.

Minimum installation and handling temperature: + 0 °C

Maximum operating temperature: 90° C on the conductor.

Minimum usage temperature: - 15 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 250° C on the conductor (for maximum 5 seconds).

Minimum permissible bending radii: 4 times the cable overall diameter.

Maximum pulling force during laying: 5 kg/mm² of the conductor cross section.

Current carrying capacity: see CEI-UNEL 35024, 35026.

Guide to Use: for internal installations, also in wet locations and for external installations; for installation in surface mounted or on metallic structures; direct laying in earth permitted.

See also the guide to use standard CEI 20-67.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.