H05V2-U

Single-core PVC insulated, non-sheathed power cable with solid conductor for internal wiring of appliances with a maximum continuous operating temperature of 90 °C.

.
.
 
 

H05V2-U Single-core solid conductor up to 1 mm² 

Rated voltage: Uo/U  300/500 V

Standards: EN 50525-1, EN 50525-2-31, EN IEC 60332-1-2, EN IEC 60228.

European directives: 2014/35/UE (LVD) - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: solid annealed plain copper class 1 (EN IEC 60228).

Insulation: PVC of type TI3.

Insulation colours:
blue, dark blue, black, brown, grey, green/yellow, red, white, turquoise, violet, orange, pink, green, yellow and all the bicolour combinations of these colours;

Marking: continuous marking on the insulation: on one side « ICEL H05V2-U IEMMEQU <HAR> ECOGAMMA »,
on the opposed side « nominal cross section, year of production, MADE IN ITALY ».

Maximum operating temperature: 90 °C on the conductor; the temperature to which the cable is exposed may be due to high ambient temperature of the installation and/or by the heat generated by the appliances in which the cables are installed.

Minimum installation and handling temperature: + 5 °C

Minimum usage temperature: - 10 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 160 °C on the conductor (for maximum 5 seconds).

Minimum internal bending radii: 4 times the overall diameter.

Maximum tensile stress: 5 kg/mm² of the conductor cross section.

Current carrying capacity: see EN 50565-1 standard and CEI-UNEL 35024.
For sections up to 1 mm²:
section (mm²) 0,5 - 0,75 - 1
current (A)          3   -   6   -   10

Guidance for Use:
For fixed and protected installations inside electrical appliances in which the wiring will operate in high temperature areas.

Further instructions and guidance for use are given in the EN 50565 standard.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.

 
.